Armoured power cables

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
YKYFty
YKYFtyn
YnKYFtyn
yKYFtY
yKYFtYn
PN-93/E-90401
IEC 60502-1
2
3 ÷ 4
5
0,6/1kV1,5 ÷ 50
1,5 ÷ 300
1,5 ÷ 240
YAKYFty
YAKYFtyn
YAnKYFtyn
yAKYFtY
yAKYFtYn
PN-93/E-90401
IEC 60502-1
3
4
3 + 1
0,6/1kV10 ÷ 300
10 ÷ 300
25+16 do 300+150

Application

Power cables with PVC insulation, filling sheath, armoured with steel tapes, and PVC outer sheath. Designed for the electrical power industry, for indoor and outdoor installation, in overhead lines, in cable ducts and directly in the ground, in areas with high exposure to mechanical stresses. Yn – fireretardant outer sheath. Ft – armour from galvanised steel tapes. Ftl – armour from painted steel tapes.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
YKYFoy
YKYFoyn
YnKYFoyn
yKYFoY
yKYFoYn
YKYFpy
YKYFpyn
YnKYFpyn
yKYFpY
yKYFpYn
PN-93/E-90401
IEC 60502-1
2
3 ÷ 4
5
3+1
0,6/1kV1,5 ÷ 50
1,5 ÷ 300
1,5 ÷ 240
25+16 do 300+150

Application

Multiconductor power cables with PVC insulated copper conductors, PVC sheath, armour from galvanised circular (Fo) or flat (Fp) steel wires and extruded PVC jacket on the armour. Designed for electricity transmission, e.g., power lines suspended in the air, indoor and outdoor installation, in cable ducts and directly in the ground in areas with high exposure to mechanical stresses.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
YAKYFoy
YAKYFoyn
YnAKYFoyn
yAKYFoY
yAKYFoYn
YAKYFpy
YAKYFpyn
YnAKYFpyn
yAKYFpY
yAKYFpYn
PN-93/E-90401
IEC 60502-1
3
4
5
3+1
0,6/1kV10 ÷ 300
10 ÷ 300
10 ÷ 240
25+16 do 300+150

Application

Multiconductor power cables with PVC insulated aluminium conductors, PVC sheath, armour from galvanised circular (Fo) or flat (Fp) steel wires and extruded PVC jacket on the armour. Designed for electricity transmission, e.g., power lines suspended in the air, indoor and outdoor installation, in cable ducts and directly in the ground in areas with high exposure to mechanical stresses.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
YKYAoy
YKYAoyn
YnKYAoyn
yKYAoY
yKYAoYn
YAKYAoy
YAKYAoyn
YnAKYAoyn
yAKYAoY
yAKYAoYn
IEC 60502-110,6/1kV50 ÷ 1000

Application

Singleconductor power cables with PVC insulated copper or aluminium conductors, PVC sheath, armour from galvanised circular (Ao) aluminium wires and extruded PVC jacket on the armour. Designed for electricity transmission, e.g., power lines suspended in the air, indoor and outdoor installation, in cable ducts and directly in the ground in areas with high exposure to mechanical stresses.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
YKYektmy
YKYektmyn
YnKYektmyn
yKYektmY
yKYektmYn
ynKYektmYn
PN-93/E-90400
PN-HD 603 S1
IEC 60502-1
2
3
4
5
0,6/1kV1 ÷ 16
1 ÷ 16
1 ÷ 16
1 ÷ 10

Application

Copper cables with PVC insulation and: – YKYektmy cables with inner PVC sheath, Cu tape screen and PVC jacket. – yKYektmY cables with filling sheath, Cu tape screen and outer PVC sheath. – yn, Yn – fireretardant. They are designed for instrumentation and control devices used in the power industry and for electricity transmission in conditions where the transmitted signals have to be protected against external interference and where the emission of interference from the cable has to be limited. Installation: in cable ducts, on structures and directly in the ground, in areas with high exposure to mechanical stresses.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
YKSYFty
YKSYFtyn
YnKSYFtyn
yKSYFtY
yKSYFtlY
yKSYFtYn
ynKSYFtYn
PN-93/E-90403
PN-93/E-90400
PN-HD 627 S1
IEC 60502-1
7 ÷ 75
7 ÷ 10
0,6/1kV1,0 ÷ 2,5
4 ÷ 10

Application

Copper signal cables with PVC insulation and: yKSYFtYn – with filling coating, galvanised steel tape armour and PVC outer sheath. YKSYFtyn – with PVC inner sheath, armoured with galvanised steel tapes, and PVC outer sheath. yn, Yn – fireretardant. Ftl – armoured with painted steel tapes. Designed for instrumentation and control devices used in the power industry and for electricity transmission. Installation: in cable ducts, on structures and directly in the ground, in areas with high exposure to mechanical stresses.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
YKSYFoy
YKSYFoyn
YnKSYFoyn
yKSYFoY
yKSYFoYn
ynKSYFoYn
PN-93/E-90403
PN-93/E-90400
PN-HD 627 S1
IEC 60502-1
7 ÷ 75
7 ÷ 10
0,6/1kV1,0 ÷ 2,5
4 ÷ 10

Application

Copper signal cables with PVC insulation and: yKSYFoY – with filling coating, galvanised steel wire armour and PVC outer sheath. YKSYFoy – with PVC inner sheath, armoured with galvanised steel wires, and PVC outer sheath. yn, Yn – fireretardant. They are designed for instrumentation and control devices used in the power industry and for electricity transmission. Installation: in cable ducts, on structures and directly in the ground, in areas with high exposure to mechanical stresses.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
YKSXSFty
YKSXSFtyn
YnKSXSFtyn
YKSXSFoy
YKSXSFoyn
YnKSXSFoyn
PN-93/E-90403
PN-93/E-90400
PN-HD 627 S1
IEC 60502-1
7 ÷ 75
7 ÷ 10
0,6/1kV1 ÷ 2,5
4 ÷ 10

Application

Copper signal cables with XLPE insulation and: – yKSXSFtYn – with filling sheath, armoured with galvanised steel tapes, with PVC outer sheath. – YKSXSFtyn – with inner filling sheath, armoured with galvanised steel tapes, with PVC outer sheath. – yn, Yn – fireretardant. – Foy – circularwire armour. – Ftl – armour from painted steel tapes. Designed for instrumentation and control devices used in the power industry and for electricity transmission. Installation: in cable ducts, on structures and directly in the ground, in areas with high exposure to mechanical stresses.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
YKSYektmy
YKSYektmyn
YnKSYektmyn
yKSYektmY
yKSYektmYn
ynKSYektmYn
PN-93/E-90400
PN-HD 627
IEC 60502-1
7 ÷ 75
7 ÷ 10
0,6/1kV1 ÷ 2,5
4 ÷ 10

Application

Copper signal cables with PVC insulation and: – YKSYektmy cables with inner PVC sheath, Cu tape screen and PVC jacket. – yKSYektmY cables with filling sheath, Cu tape screen and outer PVC sheath. – yn, Yn – fireretardant. They are designed for instrumentation and control devices used in the power industry and for electricity transmission in conditions where the transmitted signals have to be protected against external interference and where the emission of interference from the cable has to be limited. Installation: in cable ducts, on structures and directly in the ground, in areas with high exposure to mechanical stresses.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
NYRYDIN VDE 02712 ÷ 5
2 ÷ 40
2 ÷ 19
0,6/1kV1,5 ÷ 16
1,5 ÷ 2,5
4
NYRGYDIN VDE 02714
3+1
0,6/1kV25 ÷ 300
1-CYKYDYAdapted to:CSN 34 76154
4 ÷ 5
4 ÷ 7
3 ÷ 24
3+1
0,6/1kV25 ÷ 300
6 ÷ 16
4
1,5 ÷ 2,5
25+16÷240+120

Application

Power cables with PVC insulation and sheath, armoured with galvanised steel wires, designed for electricity transmission, directburied, installed in cable ducts, indoors and outdoors, where resistance against mechanical damage is required.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
NYFGY
NAYFGY
DIN VDE 02714
3 ÷ 1
0,6/1kV35 ÷ 300
25/16 ÷ 300/150

Application

Power cables with PVC insulation and sheath, armoured with flat galvanised steel wires.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
NYBYDIN VDE 02713 + 5
3 + 1
2 ÷ 40
2 ÷ 19
0,6/1kV1,5 ÷ 240
25+16 ÷ 240+120
1,5 ÷ 2.54
CBbT-cBDS 16291-852
3 ÷ 5
6 ÷ 37
6 ÷ 10
0,6/1kV1,5 ÷ 16
1,5 ÷ 240
1,5 ÷ 2.5
4 ÷ 10

Application

Power cables with PVC insulation, armoured with galvanised steel tapes.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
Cu/PVC/AWA/
PVC
BS 6346
IEC 60502-1
10,6/1kV50 ÷ 1000

Application

Singleconductor power cables with PVC insulation and sheath, armoured with aluminium wires.

SYMBOLNORMALICZBA ŻYŁNAPIĘCIEPRZEKRÓJ ŻYŁ [w mm2]
Cu/PVC/SWA/PVCBS 6346
IEC 60502-1
2
3 ÷ 4
3 + 1
5
7 ÷ 48
7 ÷ 19
0,6/1kV1,5 ÷ 240
1,5 ÷ 300
25+16÷300+150
1,5 ÷ 70
1,5 ÷ 2.5
4

Application

Multiconductor power cables with PVC insulation and sheath, armoured with galvanised aluminium wires.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
Cu/XLPE/PVC/
AWA/PVC
BS 5467
IEC 60502-1
10,6/1kV50 ÷ 1000

Application

Singleconductor power cables with XLPE insulation and sheath, armoured with galvanised aluminium wires.

SYMBOLSTANDARDNO. OF CONDUCTORSVOLTAGECONDUCTOR CROSSSECTION [in mm2]
Cu/XLPE/PVC/
SWA/PVC
BS 5467
IEC 60502-1
2÷4
3 + 1
5
7 ÷ 48
7 ÷ 19
0,6/1kV1,5÷240
25+16 ÷ 240+120
1,5 ÷ 70
1,5 ÷ 2.5
4

Application

Multiconductor power cables with XLPE insulation and PVC sheath, armoured with aluminium wires.